A sample above an EPA limit

439 WSC: PFAS in the water

Serves about 7,836 people · Purchased surface water · Sampled 2023-01 to 2025-04 · 23 samples at 3 locations. Public water system TX0140076, Texas.

EPA test results (UCMR 5)

ChemicalAverage*HighestLevelStatus
PFOSPerfluorooctanesulfonic acid3.4avg13.7max4 pptEPA limit (MCL)One or more samples above1 of 12 samples
PFHxSPerfluorohexanesulfonic acid6.2avg16.4max10 pptEPA 2024 limit, proposed for repealOne or more samples above7 of 12 samples
PFBSPerfluorobutanesulfonic acid2.9avg4.7max2,000 pptEPA health-based value (Hazard Index)Detected, below level5 of 12 samples
PFBAPerfluorobutanoic acid4.3avg10.7max7,000 pptUSGS health-based screening levelDetected, below level7 of 12 samples
PFHxAPerfluorohexanoic acid2.8avg11max4,000 pptUSGS health-based screening levelDetected, below level1 of 12 samples
PFPeAPerfluoropentanoic acid3.4avg10maxNo federal levelDetected (no federal level)4 of 12 samples
PFHpAPerfluoroheptanoic acid1.4avg5.4maxNo federal levelDetected (no federal level)1 of 12 samples

22 of 29 PFAS tested were not detected. *Highest sampling-location average (non-detects counted as 0), the way EPA compares UCMR 5 data to the PFAS limits. PFAS in parts per trillion (ppt = ng/L); lithium in µg/L.

Hazard Index (PFHxS, PFNA, GenX, PFBS) from location averages: 0.63 (2024 limit 1.0, proposed for repeal).

Filters certified for what was found

Here, PFAS were detected. Look for a filter certified to NSF/ANSI 53 or 58 with a PFOA/PFOS claim.

Certification tests use PFOA/PFOS levels far above tap water and do not yet show reduction down to 4 ppt. Replace cartridges on schedule. Check the model number on the certifier's site (IAPMO, NSF, WQA). As an Amazon Associate we earn from qualifying purchases. How we pick filters

Health-based violations since 2016

From EPA SDWIS. "Resolved" or "Archived" means the state closed it out.

ZIP codes served

76513 76543 76548 76559