6 PFAS detected, below EPA limits
Fort Drum: PFAS in the water
Serves about 34,000 people · Purchased surface water · Sampled 2024-02 to 2024-11 · 8 samples at 2 locations. Public water system NY2212214, New York.
EPA test results (UCMR 5)
| Chemical | Average* | Highest | Level | Status |
|---|---|---|---|---|
| PFHxSPerfluorohexanesulfonic acid | 4avg | 5max | 10 pptEPA 2024 limit, proposed for repeal | Detected, below level2 of 6 samples |
| PFBAPerfluorobutanoic acid | 7.5avg | 8max | 7,000 pptUSGS health-based screening level | Detected, below level2 of 6 samples |
| PFHxAPerfluorohexanoic acid | 12.5avg | 13max | 4,000 pptUSGS health-based screening level | Detected, below level2 of 6 samples |
| PFPeAPerfluoropentanoic acid | 25avg | 25max | No federal level | Detected (no federal level)2 of 6 samples |
| PFHpAPerfluoroheptanoic acid | 4avg | 4max | No federal level | Detected (no federal level)2 of 6 samples |
| 6:2 FTS6:2 Fluorotelomer sulfonic acid | 19.5avg | 26max | No federal level | Detected (no federal level)2 of 6 samples |
23 of 29 PFAS tested were not detected. *Highest sampling-location average (non-detects counted as 0), the way EPA compares UCMR 5 data to the PFAS limits. PFAS in parts per trillion (ppt = ng/L); lithium in µg/L.
Hazard Index (PFHxS, PFNA, GenX, PFBS) from location averages: 0.40 (2024 limit 1.0, proposed for repeal).
Filters certified for what was found
Here, PFAS were detected. Filter certifications name PFOA and PFOS, which were not detected here. Shorter-chain PFAS like PFBA pass through carbon filters more easily, so reverse osmosis is the more reliable choice.
Certification tests use PFOA/PFOS levels far above tap water and do not yet show reduction down to 4 ppt. Replace cartridges on schedule. Check the model number on the certifier's site (IAPMO, NSF, WQA). As an Amazon Associate we earn from qualifying purchases. How we pick filters
Health-based violations since 2016
From EPA SDWIS. "Resolved" or "Archived" means the state closed it out.
- 2017-04-01 TTHM Stage 2 Disinfectants and Disinfection Byproducts Rule · measured 83.2 UG/L Resolved
- 2017-01-01 TTHM Stage 2 Disinfectants and Disinfection Byproducts Rule · measured 90.2 UG/L Resolved