PFOA/PFOS average above EPA limit
Robeson County Water System: PFAS in the water
Serves about 67,970 people · Groundwater · Sampled 2023-02 to 2023-07 · 24 samples at 12 locations. Public water system NC0378055, North Carolina.
EPA test results (UCMR 5)
| Chemical | Average* | Highest | Level | Status |
|---|---|---|---|---|
| PFOAPerfluorooctanoic acid | 26avg | 30max | 4 pptEPA limit (MCL) | Average above EPA limit6 of 24 samples |
| PFOSPerfluorooctanesulfonic acid | 5.8avg | 6.1max | 4 pptEPA limit (MCL) | Average above EPA limit2 of 24 samples |
| PFHxSPerfluorohexanesulfonic acid | 8.3avg | 8.4max | 10 pptEPA 2024 limit, proposed for repeal | Detected, below level2 of 24 samples |
| HFPO-DAHFPO-DA (GenX chemicals) | 33.5avg | 34max | 10 pptEPA 2024 limit, proposed for repeal | Average above 2024 limit2 of 24 samples |
| PFBSPerfluorobutanesulfonic acid | 8.3avg | 8.5max | 2,000 pptEPA health-based value (Hazard Index) | Detected, below level2 of 24 samples |
| PFBAPerfluorobutanoic acid | 10.2avg | 11max | 7,000 pptUSGS health-based screening level | Detected, below level2 of 24 samples |
| PFHxAPerfluorohexanoic acid | 24avg | 25max | 4,000 pptUSGS health-based screening level | Detected, below level5 of 24 samples |
| PFPeAPerfluoropentanoic acid | 28avg | 29max | No federal level | Detected (no federal level)6 of 24 samples |
| PFHpAPerfluoroheptanoic acid | 14.5avg | 16max | No federal level | Detected (no federal level)4 of 24 samples |
| PFPeSPerfluoropentanesulfonic acid | 4.5avg | 4.7max | No federal level | Detected (no federal level)2 of 24 samples |
| lithiumLithium | 6avg | 12max | 10 µg/LEPA health reference level | One or more samples above1 of 24 samples |
19 of 29 PFAS tested were not detected. *Highest sampling-location average (non-detects counted as 0), the way EPA compares UCMR 5 data to the PFAS limits. PFAS in parts per trillion (ppt = ng/L); lithium in µg/L.
Hazard Index (PFHxS, PFNA, GenX, PFBS) from location averages: 4.19 (2024 limit 1.0, proposed for repeal).
Filters certified for what was found
Here, PFAS were detected, radium/radionuclide violations are on record. Look for a filter certified to NSF/ANSI 53 or 58 with a PFOA/PFOS claim. Reverse osmosis also reduces radium, arsenic and nitrate when its listing names them.
Certification tests use PFOA/PFOS levels far above tap water and do not yet show reduction down to 4 ppt. Replace cartridges on schedule. Check the model number on the certifier's site (IAPMO, NSF, WQA). As an Amazon Associate we earn from qualifying purchases. How we pick filters
Health-based violations since 2016
From EPA SDWIS. "Resolved" or "Archived" means the state closed it out.
- 2019-07-01 Combined Radium (-226 and -228) Radionuclides and Revised Rad Rule · measured 5.6 PCI/L Resolved
ZIP codes served
28301 28319 28340 28357 28358 28359 28360 28364 28369 28371 28372 28375 28377 28378 28383 28384 28386