PFOA/PFOS average above EPA limit

Georgetown Water Department: PFAS in the water

Serves about 7,259 people · Groundwater · Sampled 2025-03 to 2025-10 · 4 samples at 2 locations. Public water system DE0000592, Delaware.

EPA test results (UCMR 5)

ChemicalAverage*HighestLevelStatus
PFOAPerfluorooctanoic acid18avg36max4 pptEPA limit (MCL)Average above EPA limit3 of 4 samples
PFOSPerfluorooctanesulfonic acid13.5avg14max4 pptEPA limit (MCL)Average above EPA limit3 of 4 samples
PFHxSPerfluorohexanesulfonic acid5avg5.1max10 pptEPA 2024 limit, proposed for repealDetected, below level2 of 4 samples
PFNAPerfluorononanoic acid17.5avg20max10 pptEPA 2024 limit, proposed for repealAverage above 2024 limit3 of 4 samples
PFBSPerfluorobutanesulfonic acid7.5avg7.5max2,000 pptEPA health-based value (Hazard Index)Detected, below level2 of 4 samples
PFBAPerfluorobutanoic acid12avg24max7,000 pptUSGS health-based screening levelDetected, below level1 of 4 samples
PFHxAPerfluorohexanoic acid34avg68max4,000 pptUSGS health-based screening levelDetected, below level3 of 4 samples
PFPeAPerfluoropentanoic acid55avg110maxNo federal levelDetected (no federal level)3 of 4 samples
PFHpAPerfluoroheptanoic acid19.5avg39maxNo federal levelDetected (no federal level)3 of 4 samples
6:2 FTS6:2 Fluorotelomer sulfonic acid90avg180maxNo federal levelDetected (no federal level)1 of 4 samples
8:2 FTS8:2 Fluorotelomer sulfonic acid15avg30maxNo federal levelDetected (no federal level)1 of 4 samples

18 of 29 PFAS tested were not detected. *Highest sampling-location average (non-detects counted as 0), the way EPA compares UCMR 5 data to the PFAS limits. PFAS in parts per trillion (ppt = ng/L); lithium in µg/L.

Hazard Index (PFHxS, PFNA, GenX, PFBS) from location averages: 2.26 (2024 limit 1.0, proposed for repeal).

Filters certified for what was found

Here, PFAS were detected. Look for a filter certified to NSF/ANSI 53 or 58 with a PFOA/PFOS claim.

Certification tests use PFOA/PFOS levels far above tap water and do not yet show reduction down to 4 ppt. Replace cartridges on schedule. Check the model number on the certifier's site (IAPMO, NSF, WQA). As an Amazon Associate we earn from qualifying purchases. How we pick filters

Health-based violations since 2016

From EPA SDWIS. "Resolved" or "Archived" means the state closed it out.

No health-based violations recorded in EPA SDWIS since 2016.

ZIP codes served

19947

Where to read more