A sample above an EPA limit

PFAS in Clinton, IA drinking water

2 public water systems serving ZIP codes in and around Clinton were tested by EPA for 29 PFAS and lithium. PFAS found in at least one: PFOA, PFBS, PFBA, PFPeA, PFMPA, PFMBA.

ZIP codes

52732

Water systems

Iowa-American Wtr Co-Davenport

Serves about 147,720 people · Surface water · Sampled 2023-02 to 2023-11 · 4 samples at 1 location · PWS ID IA8222001

A sample above an EPA limit

ChemicalAverage*HighestLevelStatus
PFOAPerfluorooctanoic acid1.4avg4.1max4 pptEPA limit (MCL)One or more samples above1 of 3 samples
PFBAPerfluorobutanoic acid13.5avg14.8max7,000 pptUSGS health-based screening levelDetected, below level3 of 3 samples

27 of 29 PFAS tested were not detected. *Highest sampling-location average (non-detects counted as 0), the way EPA compares UCMR 5 data to the PFAS limits. PFAS in parts per trillion (ppt = ng/L); lithium in µg/L.

Health-based violations since 2016 (0)

No health-based violations recorded in EPA SDWIS since 2016.

Full report for Iowa-American Wtr Co-Davenport →

Iowa-American Wtr Co-Clinton District

Serves about 24,769 people · Groundwater · Sampled 2023-04 to 2023-10 · 9 samples at 4 locations · PWS ID IA2326048

5 PFAS detected, below EPA limits

ChemicalAverage*HighestLevelStatus
PFBSPerfluorobutanesulfonic acid11.1avg11.7max2,000 pptEPA health-based value (Hazard Index)Detected, below level2 of 8 samples
PFBAPerfluorobutanoic acid647avg648max7,000 pptUSGS health-based screening levelDetected, below level2 of 8 samples
PFPeAPerfluoropentanoic acid17.6avg18.1maxNo federal levelDetected (no federal level)2 of 8 samples
PFMPAPerfluoro-3-methoxypropanoic acid9.8avg10.4maxNo federal levelDetected (no federal level)2 of 8 samples
PFMBAPerfluoro-4-methoxybutanoic acid3avg3maxNo federal levelDetected (no federal level)2 of 8 samples
lithiumLithium59.1avg67.4max10 µg/LEPA health reference levelAbove screening level6 of 8 samples

24 of 29 PFAS tested were not detected. *Highest sampling-location average (non-detects counted as 0), the way EPA compares UCMR 5 data to the PFAS limits. PFAS in parts per trillion (ppt = ng/L); lithium in µg/L.

Health-based violations since 2016 (0)

No health-based violations recorded in EPA SDWIS since 2016.

Full report for Iowa-American Wtr Co-Clinton District →

Filters certified for what was found

Here, PFAS were detected, lithium averaged above EPA's screening level. Look for a filter certified to NSF/ANSI 53 or 58 with a PFOA/PFOS claim.

Certification tests use PFOA/PFOS levels far above tap water and do not yet show reduction down to 4 ppt. Replace cartridges on schedule. Check the model number on the certifier's site (IAPMO, NSF, WQA). As an Amazon Associate we earn from qualifying purchases. How we pick filters